Air Circuit Breaker (3Ø, 440V, 3pole, 50Hz ACB 3φ fixed type 400 A)

This set up is designed to study the working principle of ACB and to test the ACB (Air circuit breaker ) under over current fault and Earth Fault conditions . This set up consists of

  1. ACB ( Air Circuit Breaker)
  2. ACB Test Kit with Panel set up
  1. ACB (Air Circuit Breaker)

 Specification

  •  Name             :           Air circuit Breaker
  • Type             :           Non Draw out Type (Fixed)
  • Rated Current             :           400A
  • Rated Voltage             :           415V, 3 Phase, 50HZ
  • Rated Insulated Voltage             :           690 V
  • Rated S.C Breaking             :           6 KA
  • of Pole             :           Three Pole
  • Rated Making Capacity             :           77 KA (Peak)
  • Rated (S.T.) Withstand capacity :           5 sec                         :           36.6 KA ;1.0 sec                         :           25.0KA
  • Make :           HPL

 Other Features

Housing: The ACB is housed in M.S. Cubicle box with conduit plugs are provided with side entry of cables. Provision for termination of contacts is made inside the cable box

 Test Panel

Panel with ACB Test set up (current injection source)

This panel consists of the following components

  1. Meter with Relay
  2. Variable ac current source with trip time indicator /meter
  3. Earth Fault SIMULATOR

 Specification

  • One number of IDMT OC Relay with necessary CT
  • One number of Electromechanical Type Earth Fault Relay with necessary CT
  1. Over Current Relay
  • Type                                     :           Single Pole /element Over CurrentRelay
  • CT Input                                     :           5A
  • PMS                                     :           50% -200% in steps of 25%
  • TMS                                     :           1 to 1 in steps of 0.1s
  • Function                                     :           IDMT
  • Curve                                     :           IDMT curve of 3sec as per IEC-255
  • Features                                     :           Self powered
  • Hand reset type-Mechanical Flag Indicator
  • Make                                     :           MEGAWIN (MCDG11)/AREVA(CDG11)
  • One number of IDMT E/F Relay with necessary CT

E/F Current Relay

  • Type                                     :           Single Pole /element E/F Relay
  • CT Input                                     :           2A
  • PMS                                     :           50% -200% in steps of 25%
  • TMS                                     :           1 to 1 in steps of 0.1s
  • Function                                     :           IDMT
  • Curve                                     :           IDMT curve of 3sec as per IEC-255
  • Features                                     :           Self powered
  • Hand reset type-Mechanical Flag Indicator
  • Make                                     :           MEGAWIN (MCDG11)/AREVA (CDG11)
Variable ac current source with trip time indicator /meter
  • One number of Variable current source of 0-30A is provided to test ACB
  • One number of digital AC Ammeter is provided to indicate the Fault current in Amp
  • Autotransformer is provided to adjust the current output.
  • One number of Automatic trip time measurement circuit (ATTM Circuit) is provided
    • One number START push button is provided in ATTM Circuit
    • One number STOP push button is provided in ATTM Circuit
    • One number LCD – Digital stop Clock is provided in ATTM Circuit to measure relay trip time in S , S/10 , S/100
    • One number reset switch is provided in front panel to restart the digital stop clock
  1. Earth Fault Simulator

This set up is designed to simulate the Earth Fault for ACB testing , This set up consists of

  • One number of 3 phase induction motor /0.5HP/CG Make/3 PHASE 415VAC/ is provided to simulate Earth Fault
  • Necessary Earth side CT & all necessary terminals are terminated in motor for Earth Fault simulation
  • One number of Current limit resistor is provided to adjust/limit the Earth Fault current

 Other Features

  •  ACB busbar input & output indicator is provided
  • Necessary CT With suitable rating is provided
  • Breaker trip status indicator with manual on/off switch
  • All are mounted on a nice cabinet with diagram stickered on front panel.&230VAC@50Hz AC Input with power ON/OFF Switch
  • Mimic diagram is printed on panel front plate for easy understanding

 EXPERIMENTS

  •  Testing of ACB under Over current fault conditions (under different fault current & study the tripping characteristics)
  • Testing of ACB under Earth fault conditions (under different fault current & study the tripping characteristics)
  • Study the construction & operation of ACB ( AIR CIRCUIT BREAKER)